EOLO 2 loop addressed digital panel
Hardware Features
- 16 bit microprocessor analog unit
- 2 digital protocol addressed analog loops with open or closed configuration
- 240 detectors/modules per loop.
- 40×2 character LCD display with back-light function
- Touch keypad with 25 function keys
- 2 open or closed loops
- Loop short circuit protection.
- 17 frontpanel LEDS
- 1 supervised sounder output (24Vdc 1A)
- 1 supervised output to trigger the fire alarm signal devices or the activation of the extinguisher devices
- 1 fault relay output with floating contacts -1A 30Vdc 120 V ac
- 1 excluded sensors/modules/areas relay output with floating contacts -1A 30Vdc 120 V ac
- 1 technological relay output with floating contacts -1A 30Vdc 120 V ac
- 1 RS 485 serial line for connection to remote panels and printer
- 1 RS 232C serial line for centralization, remote management and remote programming with CEI 79/5, 79/6 protocol)
- 1 alarm relay output with floating contract output
- Programming data stored on non volatile EEPROM memories n. 2 17aH capacity accumulators with temperature controlled battery charger
- Warning signals for:
- 230 Vac power supply absence
- Battery absence
- Low battery
- Faulty battery charger
- Auxiliary power output 24 Vdc 2.5 monitored and protected against short circuits for external loads
- Management of additional conventional line via FDVMCZ100 module
- Power consumption when idle 300 mA at 12Vdc (430mA on primary 230Vac)
- Dimensions: 450x410x130 mm
- Power supply: 230Vac/27Vdc 5.6A
Functional characteristics
- Division in up to 32 detection areas
- 32 logic functions
- Historically archive of the last 385 events
- Automatic loop devices discovery
- Management of various types of detectors and analog modules:
- Optical,Thermal and mixed detectors
- Input modules
- Output modules
- Addressed buttons
- Addressed analog sounders
- Customised programming of phrases for each input
- 1 programming password
- 1 Maintenance password
- Technological functionality
- Local or remote programming using local Win SW via serial line or LAN/WAN network
- Management of gas detection
Reference Standards
- Product certified to EN54-2 and EN54-4
- Certified N° 1293-CPD-0154 standards CE Marking (EMC low voltage directive